BELMONT LAKE MARINA REPAIRS AND SERVICE - Approval for variance from the Liquid Fuels Handling Code

La traduction française de cet avis n'est pas disponible. Nous nous excusons pour le dérangement.

Type d'acte: Approval for variance from the Liquid Fuels Handling Code

Numéro du REO
019-9424
Numéro de référence du ministère
WO 14296329
Type d'avis
Instrument
Loi
Technical Standards & Safety Act, 2000
Affiché par
Technical Standards and Safety Authority (TSSA)
Étape de l'avis
Proposition
Proposition affichée
Période de consultation
Du 20 novembre 2024 au 20 décembre 2024 (30 jours) Ouvert
Dernière mise à jour

Cette consultation se termine à 23 h 59 le :
20 décembre 2024

Résumé de la proposition

BELMONT LAKE MARINA REPAIRS AND SERVICE wants to install a 4500 L. aboveground tank 12 inches (0.3 m) from the property line.

Détails de l'emplacement

Adresse du site

56 FIRE ROUTE 33
HAVELOCK, ON
K0L 1Z0
Canada

Détails de l'emplacement du site

Marina

Promoteur(s)

BELMONT LAKE MARINA REPAIRS AND SERVICE
56 FIRE ROUTE 33
HAVELOCK, ON
K0L 1Z0
Canada

Détails de la proposition

Liquid Fuels Handling Code (LFHC) Requirements that Would Not be Met:

3.2.1.1.  Tanks specified in Clause 3.1.1 shall be installed in accordance with the standard to which they have been certified, this Code, and the Ontario Fire Code (notwithstanding any exemption in the Ontario Fire Code from the Technical Standards and Safety Act, 2000). In the event of a conflict, this Code shall prevail.

Note: See Table 1 for location requirements in accordance with the Ontario Fire Code.

Table 1

Location of aboveground storage tanks

 

 

Maximum tank capacity, L

Minimum distance to a property

line or to a building on the same

property, m

250 000

3

500 000

4.5

250 0000

9

500 0000

12

over 5 000 000

15

 

 

Note: This Table has been reprinted from Table 4.3.2.A of the Ontario Fire Code

 

Why the Code Would Not be Met:

  • It will be the furthest from the lake that it possibly can be on this site.

 

Safety Assessment

  1. A letter of acceptance from the neighbors of adjacent property agreeing on the proposed 12 inches (0.3 m) distance from their property line.
  2. A permit for the replacement of an underground tank with an aboveground tank issued by Crowe Valley Conservation Authority (CVCA) including the following:

 

PROPOSAL DETAILS:

  • The existing underground fuel tank is 4,500 litres in size (footprint of 12 feet by 4 feet by 4 feet in size).
  • The proposed above ground fuel tank will also be 4,500 litres in size (footprint of 12 feet by 4 feet by 4 feet in size).
  • The proposed above ground tank will be attached to 14 feet long 5 feet wide (70ft2) 8-inch think concrete pad.
  • The distance (vertical) from annual high-water mark of .450 (on the existing water gauge) to the top of the concrete pad is 4 feet 2 inches and to the bottom of the tank itself 4 feet 6 inches.
    • The tank saddle supports are approximately 4 inches tall.
  • The distance (vertical) from annual high-water mark of .450 to the top of proposed above ground fuel tank is 9 feet.
  • The existing underground fuel tank is a vertical distance of 1 foot above .450 at the bottom of the tank and 4 feet above .450 at the top of the tank.
  • The distance (horizontal) from the southeast side of fuel tank pad to ordinary high-water mark is 24 feet at its closest point and 42 feet from the ordinary high water mark to the north side of the pad.
  • No in-water works required.

BASIS FOR CVCA APPROVAL

  • The proposed activity is not likely to affect the control of flooding.
    • The proposed development will be approximately 4 feet 6 inches from the bottom of the tank and 9 feet from the top of the tank to the ordinary high-water mark of Belmont Lake.
      • The regulatory flood elevation of Belmont Lake is 188.80masl CGDV 1928.
  • The proposed activity is not likely to affect the control of erosion.
  • The proposed activity is not likely to affect the control of unstable soil or bedrock.
  • The proposed activity is not likely to create conditions or circumstances that, in the event of a natural hazard, might jeopardize the health or safety of persons or result in the damage or destruction of property.

 

TSSA assesses that there is likely to be no environmental impact should this variance be granted.

Documents justificatifs

Consulter les documents en personne

Certains documents justificatifs peuvent ne pas être accessibles en ligne. Si tel est le cas, vous pouvez demander à consulter les documents en personne.

Veuillez communiquer avec le bureau mentionné ci-dessous pour savoir si les documents sont accessibles.

Technical Standards and Safety Authority
Address

345 Carlingview Drive
Toronto, ON
M9W 6N9
Canada

Office phone number

Commentaire

Dites-nous ce que vous pensez de notre proposition.

Vous avez des questions? Contactez la personne-ressource indiquée ci-dessous. Veuillez indiquer le numéro du REO de l’avis dans votre courriel ou votre lettre à la personne-ressource.

Lire nos politiques relatives aux commentaires et à la protection de la vie privée.

Soumettre en ligne

Soumettre par la poste

Contact

Marek Kulik

Phone number
Email address
Office
Technical Standards and Safety Authority
Address

345 Carlingview Drive
Toronto, ON
M9W 6N9
Canada

Office phone number

Communiquer avec nous

Contact

Marek Kulik

Phone number
Email address
Office
Technical Standards and Safety Authority
Address

345 Carlingview Drive
Toronto, ON
M9W 6N9
Canada

Office phone number

S'inscrire pour obtenir des avis

Nous vous enverrons des avis par courriel accompagnés de toute mise à jour liée à cette consultation. Vous pouvez modifier vos préférences relatives à l'avis en tout temps en allant à votre page de profil où se trouvent vos paramètres.

Suivre cet avis