CORP OF THE TOWN OF DEEP RIVER - Approval for variance from the Liquid Fuels Handling Code

Instrument type: Approval for variance from the Liquid Fuels Handling Code

ERO number
019-1905
Ministry reference number
SR 2852022
Notice type
Instrument
Act
Technical Standards & Safety Act, 2000
Posted by
Technical Standards and Safety Authority (TSSA)
Notice stage
Proposal
Proposal posted
Comment period
June 8, 2020 - July 8, 2020 (30 days) Closed
Last updated

This consultation was open from:

June 8, 2020
to July 8, 2020

Proposal summary

The Deep River Marina wants to be allowed to keep a gasoline dispenser in its current location, 3 metres from the door of the building.  Clause 5.1.1(c) of the Liquid Fuels Handling Code (LFHC) requires that product be dispensed at least 4.5 metres from any opening in a building to prevent vapour from entering the building.

Location details

Site address

38 PIER RD
DEEP RIVER, ON
K0J 1P0
Canada

Site location details

Marina

Site location map

The location pin reflects the approximate area where environmental activity is taking place.

View this location on a map opens link in a new window

Proponent(s)

CORP OF THE TOWN OF DEEP RIVER
100 Deep River Road
Deep River, ON
K0J 1P0
Canada

Proposal details

During a recent inspection, the inspector noted that the dispenser was too close to the door. 

 

Three metres from the building opening, the existing dispenser is located on a concrete slab and not susceptible to flooding or ice movement in this location. The dispenser is also well protected on two sides by concrete retaining walls. Moreover, dispensing does not take place at this location.

 

The dispenser is connected by aboveground steel pipe to hose reels. From the reels, marina staff pulls the hose to the floating dock to fuel the boats. The floating dock is approximately 7 metres from the building door; vapours are generated here, at the nozzle, much further than the 4.5 metres required by the LFHC.

 

In addition, moving the dispenser 4.5 metres away from the door would put the dispenser on timbers and over the water.

Supporting materials

View materials in person

Some supporting materials may not be available online. If this is the case, you can request to view the materials in person.

Get in touch with the office listed below to find out if materials are available.

Comment

Commenting is now closed.

The comment period was from June 8, 2020
to July 8, 2020

Connect with us

Sign up for notifications

We will send you email notifications with any updates related to this consultation. You can change your notification preferences anytime by visiting settings in your profile page.

Follow this notice