COSTCO WHOLESALE CANADA LTD - Approval for variance from the Liquid Fuels Handling Code

La traduction française de cet avis n'est pas disponible. Nous nous excusons pour le dérangement.

Type d'acte: Approval for variance from the Liquid Fuels Handling Code

Numéro du REO
026-0377
Numéro de référence du ministère
WO 14979944
Type d'avis
Instrument
Loi
Technical Standards & Safety Act, 2000
Affiché par
Technical Standards and Safety Authority (TSSA)
Étape de l'avis
Proposition
Proposition affichée
Période de consultation
Du 6 avril 2026 au 6 mai 2026 (30 jours) Ouvert
Dernière mise à jour

Cette consultation se termine à 23 h 59 le :
6 mai 2026

Résumé de la proposition

Costco is requesting three variances:

  1. To have 24 fuelling positions.
  2. Not to provide annual training to users; and
  3. Not to provide an automatic dispenser stop after dispensing 200 L of Class I (gasoline).

Détails de l'emplacement

Adresse du site

3525 Wyecroft Rd, Oakville
Oakville, ON
L6L 0B6
Canada

Détails de l'emplacement du site

Gas station

Carte de l'emplacement du site

L'épingle de localisation correspond à la zone approximative où a lieu l’activité environnementale.

Afficher cet emplacement sur une carte opens link in a new window

Promoteur(s)

COSTCO WHOLESALE CANADA LTD
415 WEST HUNT CLUB RD
OTTAWA, ON
K2E 1C5
Canada

Détails de la proposition

Costco is requesting three variances for the following sites:

  • 3525 Wyecroft Road, Oakville – 2027 Construction
  • 6620 Catherine Street, East Windsor – 2026 Construction
  • 351 Lyons Court, Wasaga Beach – 2026 Construction
  • Mayfield & Creditview Road, Caledon – 2027 Construction
  • Golf Links Road & Central Avenue, Thunder Bay – 2027 Construction

Please note items numbered 1,2 and 3, respectively, correspond to the numbered items under each subheading.

Liquid Fuels Handling Code (LFHC) Requirements that Would Not be Met:

  1. 6.1.2.2. At a self-serve facility, no more than 12 dispensing positions shall be simultaneously activated/supervised by one self-serve attendant.
  2. 6.1.4.2. The authorization holder shall ensure, on an annual basis, that card/key users are provided with detailed training on the requirements of this Code, including safe operating and emergency procedures. The authorization holder shall maintain a record of the training.
  3. 5.4.1.Dispensing equipment at a cardlock/keylock shall be installed to stop automatically after dispensing 200L of Class I product and after dispensing 1000L of Class II product.

Why the Code Would Not be Met

  1. Due to customer demand at Costco facilities, having only 12 fuel dispensing positions would cause long lines that may spill over onto roadways.The additional positions will provide improved traffic circulation.
  2. There is no need to train customers since the site will have attendants to direct traffic and provide general assistance to customers.
  3. The attendants will assist customers and can address spills and other emergencies immediately.

Equivalent Safety Measures

  • The site will have two roaming attendants when more than 18 fuel dispensing positions are activated to direct traffic and provide general assistance to customers as well as during fuel deliveries. The attendants will directly monitor the dispensing operations without distraction (at a typical cardlock, there are no attendants). In addition, there is closed-circuit television (CCTV) monitoring of all fueling positions.
  • The attendants can address spills and other emergencies immediately (at a typical cardlock, there are no attendants).
  • In addition to the attendants, there are five (5) Emergency Stop Devices around the site that will shut off the fuel supply when necessary. The site also has an oil/water separator to collect any spilled fuel.

TSSA has granted similar variances for other Costco sites. The other sites have been operating without incident for several years now.

Documents justificatifs

Consulter les documents en personne

Certains documents justificatifs peuvent ne pas être accessibles en ligne. Si tel est le cas, vous pouvez demander à consulter les documents en personne.

Veuillez communiquer avec le bureau mentionné ci-dessous pour savoir si les documents sont accessibles.

Technical Standards and Safety Authority
Address

345 Carlingview Drive
Toronto, ON
M9W 6N9
Canada

Office phone number

Commentaire

Dites-nous ce que vous pensez de notre proposition.

Vous avez des questions? Contactez la personne-ressource indiquée ci-dessous. Veuillez indiquer le numéro du REO de l’avis dans votre courriel ou votre lettre à la personne-ressource.

Lire nos politiques relatives aux commentaires et à la protection de la vie privée.

Soumettre en ligne

Soumettre par la poste

Contact

Marek Kulik

Phone number
Email address
Office
Technical Standards and Safety Authority
Address

345 Carlingview Drive
Toronto, ON
M9W 6N9
Canada

Office phone number

Communiquer avec nous

Contact

Marek Kulik

Phone number
Email address
Office
Technical Standards and Safety Authority
Address

345 Carlingview Drive
Toronto, ON
M9W 6N9
Canada

Office phone number

S'inscrire pour obtenir des avis

Nous vous enverrons des avis par courriel accompagnés de toute mise à jour liée à cette consultation. Vous pouvez modifier vos préférences relatives à l'avis en tout temps en allant à votre page de profil où se trouvent vos paramètres.

Suivre cet avis