2624827 ONTARIO INC - Approval for variance from the Liquid Fuels Handling Code

La traduction française de cet avis n'est pas disponible. Nous nous excusons pour le dérangement.

Type d'acte: Approval for variance from the Liquid Fuels Handling Code

Numéro du REO
019-1623
Numéro de référence du ministère
SR 2817990
Type d'avis
Instrument
Loi
Technical Standards & Safety Act, 2000
Affiché par
Technical Standards and Safety Authority (TSSA)
Étape de l'avis
Proposition
Proposition affichée
Période de consultation
Du 8 avril 2020 au 8 mai 2020 (30 jours) Fermé
Dernière mise à jour

Cette consultation a eu lieu :

du 8 avril 2020
au 8 mai 2020

Résumé de la proposition

2624827 ONTARIO INC wants to keep the VersapipeTM 4710 piping (a high-density polyethylene pipe commonly used by the natural gas industry) in place at its facility. The pipe was installed as vent piping for underground tanks and would be very expensive to dig up and replace. 

Détails de l'emplacement

Adresse du site

105 MAIN ST
PARKHILL, ON
N0M 2K0
Canada

Détails de l'emplacement du site

Gas station

Carte de l'emplacement du site

L'épingle de localisation correspond à la zone approximative où a lieu l’activité environnementale.

Afficher cet emplacement sur une carte opens link in a new window

Promoteur(s)

2624827 ONTARIO INC
5 EL CAMINO WAY
BRAMPTON, ON
L7A 3A1
Canada

Détails de la proposition

Clause 1.3.1 of the Liquid Fuels Handling Code (LFHC) requires that equipment be approved. The Underwriters Laboratories of Canada (ULC) Standard for Metallic and Nonmetallic Underground Piping for Flammable and Combustible Liquids (CAN/ULC-S679:2017) is the current standard for piping. VersapipeTM 4710 pipe is not approved to this ULC standard.

Tom Gallagher, P. Eng., of Gallagher Technical Services, was retained to perform a risk assessment on VersapipeTM 4710 pipe. In his letter, dated March 12, 2020, he concluded that, in his opinion, a VersapipeTM 4710 piping system does not pose any additional risk to the public or the environment than a CAN/ULC- S679 piping system for the following reasons:

  • VersapipeTM 4710 is made from high-density polyethylene, which is also used to manufacture other fuel components like sumps, spill boxes and jerry cans. These items are subject to long-term fuel exposure, including fuel additives and ethanol.
  • In a worse-case scenario in which the vent at the facility is blocked, the VersapipeTM 4710 piping would be subjected to a maximum of 5 per cent (10 pounds per square in gauge) of the rated pipe pressure (200 pounds per square in gauge).
  • The overfill valves on the underground tanks will protect against a tank overfill that could potentially expose the vent piping to liquid fuel.

In addition, the pipe manufacturer sent an email endorsing the use of VersapipeTM 4710 pipe for venting gasoline/diesel tanks.

Documents justificatifs

Consulter les documents en personne

Certains documents justificatifs peuvent ne pas être accessibles en ligne. Si tel est le cas, vous pouvez demander à consulter les documents en personne.

Veuillez communiquer avec le bureau mentionné ci-dessous pour savoir si les documents sont accessibles.

Commentaire

La consultation est maintenant terminée.

La période de consultation a eu lieu du 8 avril 2020
au 8 mai 2020

Communiquer avec nous

S'inscrire pour obtenir des avis

Nous vous enverrons des avis par courriel accompagnés de toute mise à jour liée à cette consultation. Vous pouvez modifier vos préférences relatives à l'avis en tout temps en allant à votre page de profil où se trouvent vos paramètres.

Suivre cet avis