ORIGINAL TRADERS ENERGY - Approval for variance from the Liquid Fuels Handling Code

La traduction française de cet avis n'est pas disponible. Nous nous excusons pour le dérangement.

Type d'acte: Approval for variance from the Liquid Fuels Handling Code

Numéro du REO
019-1650
Numéro de référence du ministère
SR 2818246
Type d'avis
Instrument
Loi
Technical Standards & Safety Act, 2000
Affiché par
Technical Standards and Safety Authority (TSSA)
Étape de l'avis
Proposition
Proposition affichée
Période de consultation
Du 14 avril 2020 au 14 mai 2020 (30 jours) Fermé
Dernière mise à jour

Cette consultation a eu lieu :

du 14 avril 2020
au 14 mai 2020

Résumé de la proposition

Original Traders Energy (OTE), a supplier and distributer petroleum products, is building a new facility at 180 Industrial Park Drive, Shannonville, Ontario, K0K 3A0. The company wants to *manifold the *Stage I vapour recovery header on the loading skid for the underground storage tanks at this site.  

*See note in Proposal Details.

Détails de l'emplacement

Adresse du site

180 INDUSTRIAL PARK DR
SHANNONVILLE, ON
K0K 3A0
Canada

Détails de l'emplacement du site

Bulk Plant for blending and distributing fuel

Carte de l'emplacement du site

L'épingle de localisation correspond à la zone approximative où a lieu l’activité environnementale.

Afficher cet emplacement sur une carte opens link in a new window

Promoteur(s)

ORIGINAL TRADERS ENERGY
1110 Hwy 54
Caledonia, ON
N3W 2G9
Canada

Détails de la proposition

Clause 4.3.1.6 of the Liquid Fuels Handling Code 2017 (LFHC) requires that vapour recovery piping not be manifolded to prevent cross-contamination of the products in storage tanks. The clause was originally intended for gas stations where operators tend to switch products depending on demand.

The OTE facility will be a bulk plant where ethanol is blended into fuel. Gasoline will be drawn from multiple tanks and blended in-line with ethanol to provide finished (i.e. blended) gasoline for loading into tank trucks.

 

When a truck is at the loading rack to be filled, the fuel management system will decide which of 12 regular gasoline pumps will start to deliver regular gasoline into the truck. At the same time, the fuel management system will start the ethanol pump, and the two products will be blended as they are dispensed into the truck.

 

Since any of the gasoline tanks can be the source of the gasoline blending component, the truck Stage I vapour recovery pipe header must have access to all 12 tanks to return the vapours from the truck compartment. To achieve this, OTE will have a four-inch vapour recovery header installed from the truck loading location and connected horizontally to the 12 regular and two premium gasoline tank vents.

 

There is no danger of cross-contamination since all the tanks contain gasoline (Class I product).

Note that, when a tank truck transfers gasoline into an underground tank, *Stage 1 vapour recovery is the process in which excess vapour is diverted back into the tank by a dedicated piping system. *Manifolding a header is the process of connecting two or more piping rods—originating from two or more underground tanks—into one merged pipe which is larger in size to accommodate adequate venting capacity from multiple tank sources.

Documents justificatifs

Consulter les documents en personne

Certains documents justificatifs peuvent ne pas être accessibles en ligne. Si tel est le cas, vous pouvez demander à consulter les documents en personne.

Veuillez communiquer avec le bureau mentionné ci-dessous pour savoir si les documents sont accessibles.

Commentaire

La consultation est maintenant terminée.

La période de consultation a eu lieu du 14 avril 2020
au 14 mai 2020

Communiquer avec nous

S'inscrire pour obtenir des avis

Nous vous enverrons des avis par courriel accompagnés de toute mise à jour liée à cette consultation. Vous pouvez modifier vos préférences relatives à l'avis en tout temps en allant à votre page de profil où se trouvent vos paramètres.

Suivre cet avis