CORP OF THE TOWN OF DEEP RIVER - Approval for variance from the Liquid Fuels Handling Code

La traduction française de cet avis n'est pas disponible. Nous nous excusons pour le dérangement.

Type d'acte: Approval for variance from the Liquid Fuels Handling Code

Numéro du REO
019-1905
Numéro de référence du ministère
SR 2852022
Type d'avis
Instrument
Loi
Technical Standards & Safety Act, 2000
Affiché par
Technical Standards and Safety Authority (TSSA)
Étape de l'avis
Proposition
Proposition affichée
Période de consultation
Du 8 juin 2020 au 8 juillet 2020 (30 jours) Fermé
Dernière mise à jour

Cette consultation a eu lieu :

du 8 juin 2020
au 8 juillet 2020

Résumé de la proposition

The Deep River Marina wants to be allowed to keep a gasoline dispenser in its current location, 3 metres from the door of the building.  Clause 5.1.1(c) of the Liquid Fuels Handling Code (LFHC) requires that product be dispensed at least 4.5 metres from any opening in a building to prevent vapour from entering the building.

Détails de l'emplacement

Adresse du site

38 PIER RD
DEEP RIVER, ON
K0J 1P0
Canada

Détails de l'emplacement du site

Marina

Carte de l'emplacement du site

L'épingle de localisation correspond à la zone approximative où a lieu l’activité environnementale.

Afficher cet emplacement sur une carte opens link in a new window

Promoteur(s)

CORP OF THE TOWN OF DEEP RIVER
100 Deep River Road
Deep River, ON
K0J 1P0
Canada

Détails de la proposition

During a recent inspection, the inspector noted that the dispenser was too close to the door. 

 

Three metres from the building opening, the existing dispenser is located on a concrete slab and not susceptible to flooding or ice movement in this location. The dispenser is also well protected on two sides by concrete retaining walls. Moreover, dispensing does not take place at this location.

 

The dispenser is connected by aboveground steel pipe to hose reels. From the reels, marina staff pulls the hose to the floating dock to fuel the boats. The floating dock is approximately 7 metres from the building door; vapours are generated here, at the nozzle, much further than the 4.5 metres required by the LFHC.

 

In addition, moving the dispenser 4.5 metres away from the door would put the dispenser on timbers and over the water.

Documents justificatifs

Consulter les documents en personne

Certains documents justificatifs peuvent ne pas être accessibles en ligne. Si tel est le cas, vous pouvez demander à consulter les documents en personne.

Veuillez communiquer avec le bureau mentionné ci-dessous pour savoir si les documents sont accessibles.

Commentaire

La consultation est maintenant terminée.

La période de consultation a eu lieu du 8 juin 2020
au 8 juillet 2020

Communiquer avec nous

S'inscrire pour obtenir des avis

Nous vous enverrons des avis par courriel accompagnés de toute mise à jour liée à cette consultation. Vous pouvez modifier vos préférences relatives à l'avis en tout temps en allant à votre page de profil où se trouvent vos paramètres.

Suivre cet avis